Details
Specifications
Model: RCF151 / RCF152
Rated Voltage:
-
RCF151: AC100V (85–110%)
-
RCF152: AC200V (85–110%)
Frequency: 50/60Hz
Power Consumption: 7VA
Contact Capacity of Devices:
-
Terminal ① (Main Valve): 100VA
-
Terminal ⑤ (Pilot Valve): 100VA
-
Terminal ⑨ (Ignition Transformer): 250VA
-
Terminal ⑧ (Alarm): 75VA
Allowable Ambient Temperature: -20°C to +60°C
Allowable Ambient Humidity: 35% – 90% RH (at ambient temperature of 40°C)
Withstand Voltage:
-
Between each terminal (excluding ④ & ⑥) and ground: AC1500V for 1 min or AC1800V for 1s
Insulation Resistance: -
50 MΩ or more (with DC500V Megger)
Lightning Surge Immunity: 3kV 1.2/50μs (IEC61000-4-5)
Mounting Direction: Reset button faces upwards or sideways
Mass: Approx. 395g
Application
For gas-fired combustion equipment with a combustion rate up to 175 kW/h or less (batch operation type).
Flame Detector Type: Flame Rod Detector
Sequence Timing
-
Pre-purge: 15 ±1 sec
-
Ignition Trial: 4 ±1 sec
-
Post-ignition: 1 ±1 sec
-
Lockout: 15 ±1 sec
-
Flame Response: 1 sec
Flame Current
-
Normal Combustion: 2–6μA (between flame rod and terminal ④)
-
Detection Threshold:
-
Flame: Maximum 1.0μA
-
Non-flame: Minimum 0.2μA
-
Key Differences Between RCF151 and RCF152:
Feature | RCF151 | RCF152 |
---|---|---|
Rated Voltage | AC100V | AC200V |
Application Power | Lower voltage setups | Higher voltage setups |
Other Specs | Identical to RCF152 | Identical to RCF151 |
Both models offer the same control logic, safety features, and operation sequences—only the rated voltage differs, allowing users to select based on their specific electrical setup.
View more about RCF 151/ RCF 152 GAS BURNER CONTROLLER on main site